1606-XLSBUFFER Buffer Module Instruction Manual
1606-XLSBUFFER Bedienungsanleitung für Puffermodule

Back-up Threshold Jumper

The buffer behaviour can be selected with the back-up threshold jumper.
Position „2-3“: If the terminal voltage falls below 22.5V (1606-XLSBUFFER24) resp. 45V (1606-

XLSBUFFER48), buffering starts and the terminal voltage will be kept at this level.
This adjustment is recommended for back-feeding loads, if the buffer module is
placed close to the load or whenever in doubt.

Position „1-2“: If the terminal voltage drops by 1V (1606-XLSBUFFER24) or 2V (1606-

XLSBUFFER48) buffering starts and the terminal voltage will be kept at this level.
If the terminal voltage drops slower than 0.54V/s (1606-XLSBUFFER24) resp.
1.1V/s (1606-XLSBUFFER48) buffering does not start before 22.5V resp. 45V.
This adjustment is recommended for any application where 22.5V or 45V are too
low for the application or when the buffer unit is placed close to the power supply.

Factory setting: position „2-3“
Missing jumper: equals position „2-3“

“Back-up Threshold” Steckbrücke

Mittels dieser Steckbrücke lässt sich das Verhalten des Pufferbetriebs einstellen.
Stellung „2-3“: Fällt die Klemmenspannung unterhalb von 22,5V (1606-XLSBUFFER24) bzw.

45V (1606-XLSBUFFER48), schaltet das Gerät in den Puffermodus und hält die
Klemmenspannung auf diesen Wert.
Diese Einstellung wird bei rückspeisenden Lasten empfohlen, wenn das
Puffermodul nahe der Last platziert ist oder in allen Zweifelsfällen.

Stellung „1-2“: Sinkt die Klemmenspannung um 1V (1606-XLSBUFFER24) oder 2V (1606-

XLSBUFFER48), schaltet das Gerät in den Puffermodus und hält die
Klemmenspannung auf diesen Wert.
Sinkt die Klemmenspannung langsamer als mit 0,54V/s (1606-XLSBUFFER24)
bzw. mit 1,1V/s (1606-XLSBUFFER48) startet die Pufferung aber erst bei 22,5V
bzw. 45V.
Diese Einstellung wird empfohlen, wenn die Spannung von 22,5V oder 45V nicht
ausreichend ist oder wenn das Puffermodul nahe am Netzgerät platziert ist.

Werkseinstellung: Stellung „2-3“, Eine fehlende Steckbrücke entspricht Stellung „2-3“

Status LED and Signal Outputs

Status LED

Active signal

Ready signal

Stand-by mode

ON

Low

High

Charging mode

1.25Hz flashing

Low

Low

Buffer mode

10Hz flashing

High

Low

Activated Inhibit

OFF

Low

Low

No input power

OFF

Low

Low

The Active and Ready signal outputs are galvanically isolated from the power port and may also
operate with an external PELV control voltage. The positive pole of the voltage must always be
connected with pin 6.
The signal outputs can be loaded with maximum 35Vdc, 10mA (1606-XLSBUFFER24) or 60Vdc,
6mA (1606-XLSBUFFER48). The signal leakage current is smaller than 50µA.

Status LED und Signalausgänge

Status LED

“Active” Signal

“Ready” Signal

Stand-by Betrieb

ON

Low

High

Ladebetrieb

1,25Hz blinkend

Low

Low

Pufferbetrieb 10Hz

blinkend

High

Low

Aktiver Inhibit

OFF

Low

Low

Keine Spannung

OFF

Low

Low

Die „Active“ und „Ready“ Signalausgänge sind galvanisch vom Laststromkreis getrennt und
dürfen auch an fremden PELV Steuerspannungen betrieben werden. Pin 6 muss dabei immer
mit dem positiven Pol der Spannung verbunden sein.
Signalbelastung maximal 35Vdc, 10mA (1606-XLSBUFFER24) oder 60Vdc, 6mA (1606-
XLSBUFFER48), Signalleckstrom < 50µA.

Inhibit Input

Buffering can be disabled or interrupted with the Inhibit input. Therefore, pin 6 has to be connected
to the positive pole of the terminal voltage or to the external PELV control voltage. Pin 9 must be
connected to the corresponding negative pole.
The unit does not buffer (or stops buffering) if the voltage between pin 6 and pin 9 is higher than
10V. Below 6V buffering is guaranteed again.
The current of the inhibit input is limited to 4mA. The voltage between pin 6 and pin 9 must not
exceed 35Vdc (1606-XLSBUFFER24) or 60V (1606-XLSBUFFER48).

„Inhibit” Eingang

Mit dem „Inhibit“ Eingang kann eine Pufferung verhindert oder vorzeitig abgebrochen werden.
Pin 6 muss hierzu mit dem positiven Pol der Klemmenspannung oder einer fremden PELV
Steuerspannung verbunden sein. Der „Inhibit“ Pin 9 muss mit dem entsprechenden negativen
Pol dieser Spannung verbunden werden.
Bei Spannungen zwischen Pin 6 und 9 größer 10V erfolgt keine Pufferung oder wird die
Pufferung sofort unterbrochen. Bei Spannungen kleiner 6V ist eine Pufferung möglich.
Der Signalstrom ist auf 4mA begrenzt. Die maximale Spannung zwischen Pin 6 und Pin 9 darf
35Vdc (1606-XLSBUFFER24) oder 60V (1606-XLSBUFFER48) nicht überschreiten.

Fig. 1 / Bild 1

Functional diagram / Funktionsschaltbild

Fig. 2 / Bild 2

Timing diagram / Zeitliches Ablaufdiagramm

Buffer Capacitor

Charger &

Inrush Limiter

Buffer

Capacitor

Buffer Capacitor

Discharger

Status
LED

7 Active

6 (+)

Ready Monitor

+

-

Active Monitor

+

-

Optokoppler

Optokoppler

8 Ready

9 Inhibit

Optokoppler

Buffer

Capacitor

Shut-Down

Input / Output

Voltage Monitor

Back-up
Level
Selector

Reverse-

Polarity

Protection

-

-

+

+

Safety and

Over-

Voltage

Protection

Chassis
Ground

t

t

Line

Voltage

t

t

Charging Mode

t

Buffer Mode

Hold-up Time of Power Supply

Standby

Mode

10Hz

1.25Hz

Output

Voltage

Ready

Signal

Active
Signal

Pin 8

Pin 7

Status

LED

Fig. 3 / Bild 3

Buffer time / Pufferzeit

Fig. 4 / Bild 4

Wiring diagrams / Anschlussdiagramme

Fig. 5 / Bild 5

Dimensions / Abmessungen

PE

L

+

-

N

Power

Supply

+

-

Load

+

-

Buffer

Module

optional

Buffer Current, typ.

0

0 0.3

3s

5

15

10

20A

0.6 0.9 1.2 1.5 1.8 2.1 2.4 2.4

a: XLSBUFFER24
b: XLSBUFFER48

a

b

Buffer Current, typ.

0

3

18s

0.5

1.5

1.0

2.0A

6

9

12

15

a

b

a: XLSBUFFER24
b: XLSBUFFER48

Signal wiring /

Signalverdrahtung

Active

6 (+)

5,1V

3mA

Inhibit

7

8

9

Ready

+ Vcc

Vcc: 10-35Vdc (XLSBUFFER24)
10-60Vdc (XLSBUFFER48)

UF20

10000059086 (version 00)

PU-366.010.38-10A