Rockwell Automation 1494V-DS200_DSX200 Disconnect (200A) Quick Installation Guide User Manual
Page 2

PN-133639
DIR 42052-143 (Version 05)
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
ATTENTION: Check for proper operation.
Go to Installation Instruction Sheet PN-47400.
Trailer Fuse Block Installation
5
Cutting Connecting Rod
N
Enclosure
Working Depth
(Inside Flange
of Enclosure to
Mounting Plate)
Mounting
Plate
Verify that disconnect switch and handle are in "OFF"
position. (Switch blades will be visible.)
Measure working depth of enclosure.
3
Connecting Rod Installation
4
Measure, mark and
cut connecting rod.
Connecting
Rod
Hitch Pin
Drive Bar
Primary Link
N minus 3-1/4"
Push rod down and
verify if rod is
approximately 1/8"
from touching bottom of
bolt head.
(If not, rotate rod up to
5 full turns)
1
1
2
3
5
6
7
8
5
6
4
2
Remove burrs
3
Rotate connecting rod into
drive bar (13) full turns.
1/8" Gap
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1494V-IN101E-EN-E - January 2013