Rockwell Automation 1203-FM1 FLEX I/O SCANport Module User Manual
Page 6

FLEX I/O SCANport
t
Module Installation Instructions
1–6
1203-5.7-- April 1996
Connection Enable Word Definition
Connection Enable Channel 2 Connection Enable Channel 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit:
Not Used
E2
Not Used
E1
Description
E1
SCANport channel 1 enable bit. When set to 1, the module will
attempt to connect to the SCANport device. When reset to 0, the
module stops communicating with the connected SCANport device.
This usually causes the device to fault.
E2
SCANport channel 2 enable bit. When set to 1, the module will
attempt to connect to the SCANport device. When reset to 0, the
module stops communicating with the connected SCANport device.
This usually causes the device to fault.
Logic Command/Analog Reference Definition
The Logic Command and Analog Reference values are defined
within the product manuals of the connected SCANport device(s).
LED Indicators
The status LEDs are located on the module’s top label.
SCANPORT
Flex I/O
1203-FM1
1
MODULE
CH1
CH2