Storage, Maintenance, Transport
Storage, Maintenance, Transport
Storage
Store the UPS covered in a cool, dry location with the battery module(s) fully charged.
At 5° to 86° F (–15° to 30° C), charge the UPS battery module every six months.
At 86° to 113° F (30° to 45° C), charge the UPS battery module every three months.
Replacing the Battery Module
This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated
from electrical hazards. You may leave the UPS and connected equipment on during the replacement
procedure.
For instruction, see applicable steps in Connecting the Battery.
Ensure battery replacement every 2-4 years.
Standard (40C) battery; Allen-Bradley catalog number: 1609-500SBAT.
Once the battery module(s) are disconnected the connected equipment is not protected from power
outages.
Refer to the appropriate replacement battery installation guide for battery module installation instructions. See
your dealer or contact Rockwell Automation at 440-646-5800 for information on replacement battery modules.
Be sure to deliver the spent battery module(s) to a recycling facility or ship it to the address
specified in the replacement battery literature.