Torque specifications, Scr module access, I-11 – Rockwell Automation 1336-SN-SP19A Snubber Board Kit, 1336-SN-SP19A User Manual

Page 11: Scr module access” on

Advertising
background image

1336-5.49 – August, 1999

I-11

Torque Specifications

The following table lists fastener locations by component,
application, and torque specifications. Refer to “Torque Sequence” on
page I-4
for fastening two-point, four-point and six-point components
to the heat sink.

SCR Module Access

Important: Before you remove connections and wires from the drive
components, mark the connections and wires to correspond with their
component connections and terminals to prevent incorrect wiring
during assembly.

Component

Fastener Application

Torque

in.-lb

Torque

N-m

Snubber Board

Board to SCR

50

6

SCR Module

Module to heat sink

50

6

Wires (PE)

Wires to Ground Stud

80

9

Wires

Wires to TB1

80

9

Wire (TE)

Wires to TB1

50

6

Wires

Wires to TB2

7

0.8

Wires

Wires to TB3

8 – 10

09 – 1.1

Power Cables

Cables to terminals

208

23

Control Board Platform

Plates to chassis

26

3

High Voltage Guard

Guard to chassis

26

3

!

ATTENTION: Disconnect and lock out power from
the drive before disassembling the drive. Failure to
disconnect power may result in death or serious injury.
Verify bus voltage by measuring the voltage between
+DC and -DC on Terminal Block TB1. Do not attempt
to service the drive until the bus voltage has discharged
to zero volts.

!

ATTENTION: Wear a wrist-type grounding strap
when servicing drives. Failure to protect drive
components against ESD may damage drive
components. Refer to “Electrostatic Discharge
Precautions” on page I-4
.