Voltage pi, Volt select, Pi config – Rockwell Automation 1336F PLUS II Custom Firmware Instructions - EN921 User Manual
Page 4

4
EN921 - Variable Voltage w/ PI Power/Current Control
Note: The “Process PI” parameter group has been eliminated in this custom firmware.
Voltage PI
This group of parameters configures the Voltage PI Regulator.
[Volt Select]
This parameter specifies which input signal will be used
as the [Volt Command] reference when [Control Select] is
set to “Variable Voltage”.
Parameter Number
337
Parameter Type
Read and Write
Factory Default
“Volt Preset”
Units
Display Drive
“Analog In 0” 0
“Analog In 1” 1
“Analog In 2” 2
“Volt Preset” 3
Refer to [Volt Preset] Value
“Adapter 1-6” 4-9
“Volt Cmd Ref” 10 Refer to [Volt Command Ref] Value
“Pre+AI0 Trim” 11 Refer to [Volt Trim%] Value
“Pre+AI1 Trim” 12
“Pre+AI2 Trim” 13
“Pre+Trim Ref” 14 Refer to [Volt Trim% Ref] Value
“Voltage PI” 15 Voltage PI Control (new selection)
[PI Config]
This parameter sets and displays the configuration for the
PI regulator.
Note: Reset Integrator (Int) is also available through a dig-
ital input.
Parameter Number
213
Parameter Type
Read/Write
Factory Default
00000000
PI Reference
PI Reference
Select
pi reference
Σ
Σ
PI Config.sqrt_fdbk
PI Config.inv_error
PI Config.reset_int
PI Feedback
PI Error
Process KI
s
Process KP
Integral Term = 0
PI Pos Limit
PI Neg Limit
PI Output
PI Voltage
Reference
Output Voltage
pi feedback
PI Feedback
Select
+
–1
–
+
+
PI Config.zero_clamp
Volt Incr/Decr Time
PI Enable
+4096
0
+4096
0
Bit 7
Bit 6 Bit 5 Bit 4
Bit 3 Bit 2 Bit 1
Bit 0
Inv Error - Changes sign of PI Error
Reset Int - Holds KI at zero
Zero Clamp - Prevents bidirectional operation
Sqrt Fdbk - Uses sq. root of PI feedback value
Set Output
0
0
0
0
1
1
Preload Int
0
0
1
1
0
0
PI Enable
0
1
0
1
0
1
Diagram
1
2
3
Bypass - Set PI Output equal to PI Ref
(Refer to Diagrams on next page)