EN921 - Variable Voltage w/ PI Power/Current Control

Note: The “Process PI” parameter group has been eliminated in this custom firmware.

Voltage PI

This group of parameters configures the Voltage PI Regulator.

[Volt Select]

This parameter specifies which input signal will be used
as the [Volt Command] reference when [Control Select] is
set to “Variable Voltage”.

Parameter Number

337

Parameter Type

Read and Write

Factory Default

“Volt Preset”

Units

Display Drive

“Analog In 0” 0
“Analog In 1” 1
“Analog In 2” 2

“Volt Preset” 3

Refer to [Volt Preset] Value

“Adapter 1-6” 4-9

“Volt Cmd Ref” 10 Refer to [Volt Command Ref] Value

“Pre+AI0 Trim” 11 Refer to [Volt Trim%] Value
“Pre+AI1 Trim” 12
“Pre+AI2 Trim” 13

“Pre+Trim Ref” 14 Refer to [Volt Trim% Ref] Value

“Voltage PI” 15 Voltage PI Control (new selection)

[PI Config]

This parameter sets and displays the configuration for the
PI regulator.

Note: Reset Integrator (Int) is also available through a dig-
ital input.

Parameter Number

213

Parameter Type

Read/Write

Factory Default

00000000

PI Reference

PI Reference

Select

pi reference

Σ

Σ

PI Config.sqrt_fdbk

PI Config.inv_error

PI Config.reset_int

PI Feedback

PI Error

Process KI

s

Process KP

Integral Term = 0

PI Pos Limit

PI Neg Limit

PI Output

PI Voltage
Reference

Output Voltage

pi feedback

PI Feedback

Select

+

–1

+

+

PI Config.zero_clamp

Volt Incr/Decr Time

PI Enable

+4096

0

+4096

0

Bit 7

Bit 6 Bit 5 Bit 4

Bit 3 Bit 2 Bit 1

Bit 0

Inv Error - Changes sign of PI Error
Reset Int - Holds KI at zero
Zero Clamp - Prevents bidirectional operation
Sqrt Fdbk - Uses sq. root of PI feedback value
Set Output

0

0

0

0

1

1

Preload Int

0

0

1

1

0

0

PI Enable

0

1

0

1

0

1

Diagram

1

2

3

Bypass - Set PI Output equal to PI Ref

(Refer to Diagrams on next page)