All parameters are specified at 24V, 20A, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
4
Rockwell Automation Publication 1606-RM026A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
5. Standby Mode
Input voltage
nom. DC
24V
Voltage range
nom. 24-28.8Vdc
Input current
typ. 80mA
Standby
mode
Power dissipation
typ. 1.9W
Status lamp
always on
Active signal
high ohmic
Ready signal
low ohmic
6. Charging Mode
Charging current
min. 0.4A
Charging
mode
max. 0.6A
Charging
mode
Charging time
min.
20s / 15s
Initial charge
1)
/ Re-charging
2)
max.
29s / 21s
Initial charge
1)
/ Re-charging
2)
Status lamp
flashes 1.25Hz
Active signal
high ohmic
Ready signal
high ohmic
1) Initial charging is the first charge after voltage is applied to the buffer unit.
2) Re-charging is the charging of the internal capacitors after voltage interruptions of less than 2 minutes.
Fig. 6-1 Re-charging time, 24V
Charge
20
0
5
10
30s
Charging Time
40
80
60
100%
15
20
25
max
min