Chapter 4, Setup and commissioning, Chapter – Rockwell Automation 1503 IntelliVAC Contactor Control Module - Series C and later User Manual
Page 36

Chapter
4
1503-UM052D-EN-P – June 2013
Setup and Commissioning
IntelliVAC Configuration
The IntelliVAC module is configured for a specific application by setting
DIP switches. They are accessed by loosening the two screws on the front
of the unit, and removing the cover by sliding it forward. The switches
are found on the front edge of the IntelliVAC circuit board (see Figure
4.1). There are 12 switches, with number 1 being at the top next to the
mini DIN connector. (Refer to Table 4.B).
S H O C K H A Z A R D
S H O C K H A Z A R D
Hazardous voltage is present inside the module
which may cause personal injury or death.
Remove all sources of power from the module
and discharge any connected capacitors before
removing the cover.
I M P O R T A N T
I M P O R T A N T
Remove power from the module before
removing the cover and before changing the
DIP switch settings. The new DIP switch
settings are recognized only on power-up.
LEDs
Ground Stud
Supply Power Input
Interface Connections
EEPROM Programming Port
(Mini DIN Connector)
DIP Switches
Status Relay Outputs
Internal Control Fuse
Figure 4.1 – DIP Switch and Connector Locations