Auxiliary contact replacement and set-up procedure – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual
Page 50

Maintenance
4-21
1502-UM051E-EN-P – June 2013
1. If replacing a single contact cartridge, remove the appropriate leads and
turn the plastic retaining screws to allow removal of the cartridge as shown
in Figures 4.25 and 4.26. Insert the new cartridge and position the retaining
screws to hold it in place. Reconnect the leads to the cartridge. Ensure that
the cartridge is in the proper configuration (the top cartridges are normally
closed, the bottom cartridges are normally open, refer to Figure 4.27). The
“normal” state is when the contactor is “off ” (open position).
To remove cartridge,
turn retaining screws.
Auxiliary contact removed
Figure 4.25 – Retaining Screws
Figure 4.26 – Cartridge Removal
Note: For Series E contactors, the top auxiliary contact position must use a
700-CP1 cartridge. All other positions must use 700-CPM cartridg-
es.
2. If replacing the entire auxiliary assembly, remove the leads from all cartridges
and remove the assembly complete with mounting plate by removing the
mounting bolts as shown in Figure 4.27.
Auxiliary Contact Replacement
and Set-Up Procedure