I/o specifications – Rockwell Automation 1336S PLUS II Analog Interface Inst. User Manual

Page 4

Advertising
background image

4

1336 PLUS II Analog Interface Option Board Installation

I/O Specifications

Specifications for the various inputs and outputs are provided below.

1

Use TB2-5 for shield connection.

2

Refer to Typical Isolation diagram below.

I/O Type

Configuration

Specification

Ref.

Standard

0-10V Input

100k ohm input impedance.

TB2-4

1

0-10V Output

Can drive a 10k ohm load (60 mA short circuit
current limit).

TB2-9

1

0-20 mA Input

200 ohm input impedance.

TB2-4

1

10k Ohm Pot. Input 760k ohm input impedance.

Pot. source = 5V through 2.67k ohms to TB2-1.

TB2-4

1

Option
Board

2

0-10V Input

100k ohm input impedance.

TB2-5

0-10V Output

Can drive 3.3k ohms (3 - parallel 10k ohm loads). TB2-5

0-20 mA Input

100 ohm input impedance.

TB2-5

0-20 mA Output

Can drive 400 ohms (3 - series 0-20 mA inputs). TB2-5

Pulse Input

250 ohms in series with an opto LED.

Pulse high is greater than 8 mA or 3.6V, while
pulse low is less than 0.8V or 0.2 mA.

Absolute maximum continuous input level is 12V
or 50 mA.

TB2-9

Pulse Output

Provides a current limited 4.5V square wave.

This output can drive one PLUS or three PLUS II
pulse inputs.

TB2-5

Thermistor Input

5V across 3.3k ohms in series with the
thermistor.

This arrangement limits the measuring voltage to
less than 2.5V (no self-heating).

TB2-4

Signal

Conditioning

Signal

Option Board

User

I/O

Power

Typical Isolation

True Galvanic Isolation to 200V AC

(greater than 10 M ohm, less than 50 pf).

Rockwell Automation helps its customers receive a superior return on their investment by bringing
together leading brands in industrial automation, creating a broad spectrum of easy-to-integrate
products. These are supported by local technical resources available worldwide, a global network
of system solutions providers, and the advanced technology resources of Rockwell.

Worldwide representation.

Argentina • Australia • Austria • Bahrain • Belgium • Bolivia • Brazil • Bulgaria • Canada • Chile • China, People’s Republic of • Colombia • Costa Rica • Croatia • Cyprus
Czech Republic • Denmark • Dominican Republic • Ecuador • Egypt • El Salvador • Finland • France • Germany • Ghana • Greece • Guatemala • Honduras • Hong Kong
Hungary • Iceland • India • Indonesia • Iran • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Macau • Malaysia • Malta • Mexico
Morocco • The Netherlands • New Zealand • Nigeria • Norway • Oman • Pakistan • Panama • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia
Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic of • Spain • Sweden • Switzerland • Taiwan • Thailand • Trinidad • Tunisia • Turkey • United Arab Emirates
United Kingdom • United States • Uruguay • Venezuela

Rockwell Automation Headquarters, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414 382-2000, Fax: (1) 414 382-4444

Publication 1336 PLUS-5.70 – July, 1998

P/N 189357 (02)

Supersedes January, 1998

Copyright 1998 Rockwell International Corporation. All rights reserved. Printed in USA.

Advertising