Rockwell Automation 1336T Master/Slave Parallel AC Drv User Manual

Page 48

Advertising
background image

1336 FORCE-5.19 – August, 2000

5-2

Encoderless Operation

◗

Torque regulation (+/-5%) is comparable with encoderless and
encoder at velocities greater than approximately 25% of base
speed. At lower speeds encoderless torque regulation may
degrade with changing motor temperature.

◗

Torque response is comparable with both encoderless and
encoder (200 Hz).

Parameter Settings

Required parameter settings that are unique to Master/Slave
Encoderless Operation are:

Master Drive:

1. Parameter 223, Precharge/Ridethru Selection, bit 7 set = 1 (M/S

encoderless enable).

2. Parameter 285, Test DAC1 = 74.

3. Parameter 88, VP Fault/Warning Configuration Selection

Bit 0 set = 0, to disable the Encoder Feedback loss fault
Bit 5 set = 0, to disable the “motor stalled” fault

4. Parameter 150, Feedback Device Type = 5, (Encoderless

velocity estimate with deadband). This should provide a speed
range of about 60:1. If a larger speed range is needed, selecting
Type = 7, (Encoderless without deadband and low bandwidth)
could be considered.

Slave Drive:

1. Parameter 223, Precharge/Ridethru Selection, bit 7 set = 1 (M/S

encoderless enable).

2. Parameter 88, VP Fault/Warning Configuration Selection

Bit 0 set = 0, to disable the Encoder Feedback loss fault
Bit 5 set = 0, to disable the “motor stalled” fault

3. Parameter 150 = 0 (Encoder Feedback Operation)