Rockwell Automation Publication 1608P-UM005A-EN-P - November 2014

Chapter 2

Installation

3-Wire vs. 4-Wire
Configurations

HC-DySC models are available for use with either 3-wire (L1, L2, L3) or 4-wire
(L1, L2, L3, N) sources. The input N conductor must be connected to 4-wire
models for proper operation. Do not connect a N conductor to 3-wire models

.

3- Wire Models

Bulletin 1608P part numbers containing V3 are configured for 3-wire source (L1,
L2, L3) and 3-wire loads (X1, X2, X3). Do not connect a N conductor to 3-wire
models.

Figure 3

shows the 3-wire HC-DySC system wiring schematically,

including the internal maintenance bypass switch

.

Figure 3 - HC-DySC 3-Wire Configuration

Note for Canadian Users: The 200 A HC-DySC models rated greater than 440V have not been
evaluated for compliance with CSA 22.2 No. 107.1-01 when connected to corner-grounded or
ungrounded delta power sources. Contact Rockwell Automation Technical Support for assistance.

L3

X3

X1

X2

L2

CB

CB

CB

Customer supplied

circuit breaker

GND

GND

CBB

CBO

CBI

G

X1

X2

X3

L1

L2

L3

L1

HC-DySC

Electronics

3-WIRE SOURCE