Rockwell Automation 1405-M620 Operating Instructions User Manual
Page 4
 
NC
NC
L3
L1
L1
N
N
GND
GND
L2
Aux. Supply
Current Inputs
Voltage Inputs
(120V or 240V only)
M620
-
-
-
Pins 2 and 4 (counting from the left side) of the 7-pin 
connector are not used: no external wires should be 
connected to these terminals!
Publication 1405-IN002C-EN-P - November 2004
4 Bulletin 1405 (M620) Operating Instructions
CT Connection: Careful consideration should be given when 
connecting the secondary of the CT to the current inputs of the 
MiniPowermonitor. Extended lengths of connection wire will cause 
the VA rating of the CT to increase and will create higher common 
mode input voltage. It is recommended that the wire size be selected 
to limit the impedance to 200 milliohms. Exceeding this limit may 
cause current readings to become less accurate when using a star 
connection.
Aux Supply: With this option, instrument power is supplied by a 
separate 120V or 240V line, independent of the measured power lines. 
A third connector block (3-pin, spring-clamp terminals type) is added 
at the rear with this option.