Mount the point i/o adapter on a din rail – Rockwell Automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual
Page 18

10
Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 2 Install Your POINT I/O or ArmorPOINT I/O Adapter
Mount the POINT I/O Adapter on a DIN Rail
1. Make sure the DIN rail locking screw (orange) is in horizontal position.
2. Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm)
top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number
199-DR1; 46277-3).
3. Press down firmly to install the adapter on the DIN rail, noting that the
locking mechanism locks the adapter to the DIN rail.
4. Set the network address thumbwheel switches to the desired value. See
for details on setting the IP address.
5. Slide the safety end cap up to remove it, exposing the backplane and power
interconnections.
ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent
equipment for adequate ventilation.
ATTENTION: Do not discard the end cap. Use this end cap to cover the
exposed interconnections on the last mounting base on the DIN rail.
Failure to do so could result in equipment damage or injury from electric
shock.
ATTENTION: This product is grounded through the DIN rail to chassis
ground. Use zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
1734-AENTR Series B
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
75.30
(2.96)
74.00
(2.91)
132.72
(5.23)
52.23
(2.06)
35.55
(1.40)
A
B
45174
A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)