Interpret the status indicators – Rockwell Automation 1738-8CFGM23 ArmorPoint Module with Configurable 24V DC Points User Manual
Page 12
Advertising

12 ArmorPoint I/O Modules with 8 Configurable 24V DC Points
Publication
1738-IN026B-EN-E - February 2010
Interpret the Status Indicators
1738-8CFGM8, 1738-8CFGM12, 1738-8CFGM23 Indicator Status
Status
Description
Module status
Off
No power applied to device
Green
Device operating normally
Flashing green
Device needs commissioning due to
missing, incomplete, or incorrect
configuration
Red
Unrecoverable fault – may require
device replacement
Flashing red
Recoverable fault
Flashing red/green
Device is in self-test
MOD
NET
1738-8CFGM8
24V DC
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
Module Status Indicator
43683
Network Status Indicator
I/O Status Indicators
1738-8CFGM8 shown
Advertising