Pre-installation considerations, Understand compliance to european union directives – Rockwell Automation 1771-IBD INSTL INSTR DC (10-30V) INPUT User Manual

Page 2

Advertising
background image

DC (10-30V) Input Module

2

Publication 1771-5.53 – April 1999

!

ATTENTION: This module is equipped with a plastic
cover that is unique to assembly numbers 960364-05
and 961344-01. (This part number is located near the
backplane edge connector pins on the component-side
of the circuit board.) Do not use this plastic cover on
any other module.

The 1771-IBD Series B module is compatible with all chassis except
1771-A1, 1771-A2, 1771-A4 chassis. Make sure no other input
module or single card block transfer module is placed in the same
module group when using 2-slot addressing. Any discrete output
module may be used within the same module group.

The 1771-IBD Series B module has a selectable off-delay filter time
of either 1ms or 6ms. To select the off-delay filter time, use the
procedure on page 3.

If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.

EMC Directive

This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards,
in whole or in part, documented in a technical construction file:

EN 50081-2EMC – Generic Emission Standard,
Part 2 – Industrial Environment

EN 50082-2EMC – Generic Immunity Standard,
Part 2 – Industrial Environment

This product is intended for use in an industrial environment.

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC
Low Voltage, by applying the safety requirements of EN 61131–2
Programmable Controllers, Part 2 – Equipment Requirements and
Tests.

For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as these Allen-Bradley
publications:

Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1

Guidelines for Handling Lithium Batteries, publication AG-5.4

Automation Systems Catalog, publication B111

This equipment is classified as open equipment and must be mounted
in an enclosure during operation to provide safety protection.

Pre-installation
Considerations

Understand Compliance to
European Union Directives

Advertising