I/o memory mapping, Spare/replacement module parts – Rockwell Automation 1769-IM12 Compact 1769-IM12 240Vdc Input Module User Manual

Page 10

Advertising
background image

10

Compact™ 240V ac Input Module

Publication 1769-IN011B-EN-P

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:

I/O Memory Mapping

Input Data File

For each input module, slot x, word 0 in the input data file contains the current
state of the field input points. For the 1769-IM12, bits 12 to 15 are not used.

r= read

Spare/Replacement Module Parts

Terminal Block:

1769-RTBN18 (1 per kit)

Door Label:

1769-RL1 (2 per kit)

Door:

1769-RD (2 per kit)

Wire Type

Wire Size

Terminal Screw

Torque

Retaining Screw

Torque

Solid

Cu-90°C (194°F)

#14 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Stranded

Cu-90°C (194°F)

#16 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)