Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual
Page 29

3–8
Installation and Wiring
Publication 1746Ć6.8 - April 1997
Wiring Schematic for SingleĆended Analog Input Connections
Transmitter
+
Transmitter
Supply
Signal
+
IN 1 +
IN 1 -
IN 3 +
IN 3 -
+
Power
Supply
-
IN 0 +
IN 0 -
IN 2 +
IN 2 -
Transmitter
+
Signal
Transmitter
+
Signal
Ground
NI8
Signal
When wiring singleĆended analog
input devices to the analog input
module, the number of total wires
necessary can be limited by
jumpering all IN-" terminals
together. Note that differential
inputs are more immune to noise
than singleĆended inputs.
Important: The module does
not provide loop power for
analog inputs. Use a power
supply that matches the
transmitter specifications.
Important: Follow the
guidelines on pages 3-
7
and
3-9
when wiring the module.
Wiring Schematics for 2, 3, and 4ĆWire Analog Input Devices
2ĆWire Transmitter
Transmitter
+
-
4ĆWire Transmitter
Transmitter
Supply
Signal
+
-
+
-
IN +
IN -
Module
IN +
IN -
Module
+
Power
Supply
-
+
Power
Supply
-
Important: The module does
not provide loop power for
analog inputs. Use a power
supply that matches the
transmitter specifications.
Important: Follow the
guidelines on pages
3-7 and
3-9 when wiring the module.
3ĆWire Transmitter
Transmitter
Supply
Signal
GND
IN +
IN -
Module
+
Power
Supply
-