Typical Wiring Guidelines

Terminal base units are rated at 10 A.

For Spring-clamp Terminal Base Units: 1794-TB3S, -TB3TS, -TB3GS, -TB32S,
-TB3SK, -TB3TSK, -TB3GSK

Insert a 2.54…3.05 mm (0.10…0.12 in.) wide-bladed screwdriver into the slot and lift up.

Insert wire, and remove screwdriver.

For Cage-clamp Terminal Base Units: 1794-TB2,

-TB3, -TB3K, -TB3T,-TB3TK, -TB3G, -TB3GK, -TB32

Tighten screws to 0.8 Nm (7 lb-in).

For Knifeswitch Cage-clamp Terminal Base Unit: 1794-TBKD

Tighten screws to 0.53 Nm (6 lb-in).

For NEMA Screw-clamp Terminal Base Units: 1794-TBN, -TBNK, -TBNF,
-TBNFK

Tighten screws to 1.02 Nm (9 lb-in).

Install or Change a Fuse in the 1794-TBNF or 1794-TBNFK Terminal Base
Unit

This terminal base unit has fuse holders for 5x20 mm fuses on each of the eight
even-numbered I/O terminals (0 through 14 - row B). To install or change a fuse:

1.

Press the fuse holder down toward the terminal strip.

2.

Remove the fuse from the fuse holder.

3.

Insert a known good 5x20 mm fuse into the fuse holder.

4.

Rotate the fuse holder back to vertical until it snaps into the locked
position.

The 1794-TBNF and 1794-TBNFK terminal base units are shipped with eight 5x20
mm, 1.6 A, 250V AC slow-blow fuses, one for each even-numbered terminal (0
through 14 on row B). These fuses are suitable for use with the 1794-OA8 AC
output module. Refer to the specific installation instructions for fusing
recommendations for your particular module.

Use the Knifeswitch Terminal Base

The knifeswitch terminal base has 16 individual mechanical-knifeswitch circuit
breakers (two for each channel). Each switch opens or closes one side (input/output
and return) for a channel.

1.

Place a small-bladed screwdriver into the slot of the knifeswitch of the I/O
point circuit that you wish to break.

2.

Rotate downward to open the circuit.

This opens the path of an individual circuit.

3.

To reestablish the circuit, rotate the knifeswitch back into the terminal base
unit until it snaps into place.

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

51

33

34

+V

COM

+V

COM

B

C

Even Numbered I/O Terminals 0 to 14

Odd Numbered I/O Terminals 1 to 15

(1794-TBN shown)

+V = Terminals C-34, C-51

COM (-V) = Terminals B-16, B-33

Wiring Connections for the 1794-TBN, 1794-TBNK, 1794-TBNF, 1794-TBNFK

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Wiring Connections for the 1794-TB3T, -TB3TS

Inputs/Outputs

(1794-TB3T shown)

+V = Supply Out - Terminals C-50, C-51

Supply
In

Supply
Out

A

B

C

C

N3

CJC

+V

C

C

C

C

C

C

C

C

C

N2

N1

N0

N7

N6

N5

N4

+V

CJC

Chassis Ground

+V) = 24V dc Supply In - Terminals C-34, C-35

Channel Channel Channel Channel Channel Channel Channel Channel

0

1

2

3

4

5

6

7

+

--

+

--

+

--

+

--

+

--

+

--

+

--

+

--

C = -V dc common

-V = 24V dc Common Terminal B-16

-V = Terminal B-33

Wiring Connections for the 1794-TB3T, - TB3TK, -TB3TS, -TB3TSK

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Inputs/Outputs

Common

-V (Common) = Terminals B-16, B-33, C-35 through C-50

+V (Voltage In) = Terminals C-34, C-51

-V

Voltage
In +V

Voltage
Out +V

B

C

Common

-V

Common

Wiring Connections for the 1794-TBKD

For daisy-chaining: Supply in - C-34 (+), B-16 (-)

Supply out - C-51 (+), B-33 (-)

CH0

CH2

CH3

CH4

CH5

CH6

CH7

CH1

CH0
RET

CH2
RET

CH3
RET

CH4
RET

CH5
RET

CH6
RET

CH7
RET

CH1
RET

Wiring Connections for the 1794-TBKD

Wiring when total current draw through base is less than 10 A.

Wiring when total current draw through base is greater than 10 A.

Modules in this configuration must be all analog or all digital.

Total current draw through any base must not be greater than 10 A.

Wiring when there is a mix of analog and digital modules.

24V dc

24V dc

24V dc

Digital Module

Digital Module

Digital Module

Thermocouple

or Analog Module

Use separate power supplies for analog and digital modules.

Press down to open.