Rockwell Automation 1786-RG6F INSTL.INSTR CONTROLNET H-FLEX User Manual
Page 5

ControlNet Standard and High-flex Coax Cable 5
Publication 1786-IN009B-EN-P - November 2003
You can increase the total trunk-cable length or number of taps by installing repeaters on the
segment. This creates another segment. The following examples explain how you can
calculate allowable lengths of segments for standard RG-6 (1786-RG6/A), and high flex
RG-6 (1786-RG6F/A) cable, as well as for a system that combines the two types of cables.
EXAMPLE
Example 1: Using only standard RG-6 cable in your system
In this example, the segment:
•
has 3 nodes (requires 3 taps)
•
uses standard 1786-RG6 cable
To calculate the allowable cable length of standard 1786-RG6/A cable:
3280 ft - (53.4 ft * [3 - 2]) = maximum length
3280 ft - 53.4 ft = 3226.6 ft (983.4 m)
EXAMPLE
Example 2: Using only RG-6F cable in your system
In this example, the segment:
•
has 16 nodes (requires 16 taps)
•
uses high-flex 1786-RG6F cable
To calculate the maximum allowable cable length of high-flex RG-6 cable
(1786-RG6F):
([20.29 dB - 16 *.32 dB] / 13.5 dB) * 1000 = 1123 ft (342.3 m)
20162-M
2570.4 ft (783.4 m)
656.2 ft (200 m)
terminator
terminator
1786-RG6 cable
tap
tap
tap
20162-M
1123 ft (342.3 m)
terminator
terminator
1786-RG6F cable
tap
tap
tap