Device Status Indicators
Indicator
Status
Description
Network
status
Off
Device is not online.
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Green
Device operating normally and is online with
connections in the established state. As a Group 2
module, it means that the module is allocated to a
master.
Flashing green
Device is online with no connections in the established
state.
Red
Critical link failure – failed communications module.
Flashing red
Recoverable fault – an I/O connection has timed out.
Module
status
Off
No power applied to the device.
Green
Device is operating normally.
Flashing green
Device needs commissioning due to missing,
incomplete, or incorrect configuration.
Flashing red
Recoverable fault – input or output short circuit.
Red
Critical fault – Device timed out or has an
unrecoverable fault.
Auxiliary
status
Off
There is no auxiliary power applied to the module.
Green
There is auxiliary power applied to the module.
I/O status
Off
Output is not energized or input is not valid.
Yellow
Output is energized or input is valid.