Rockwell Automation 1794-IB16XOB16P_IB10XOB6 Flex I/O Input/ Output Module Installation Instructions User Manual

Page 5

Advertising
background image

5

Publication 1794-IN083B-EN-P - November 2004

Derating Chart for the 1794-IB16XOB16P

General Specifications

Module Location

1794-IB10XOB6 - Cat. No. 1794-TB2, -TB3, -TB3S Terminal Base Unit
1794-IB16XOB16P - 1794-TB32, -TB32S Terminal Base Unit

Input Filter Time

2

Off to On

On to Off

0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms default - Selectable

Terminal Base Screw
Torque

7 pound-inches (0.8Nm)

Dimensions (with module
installed)

3.7H x 3.7W x 2.7D inches
94H x 94W x 69D mm

Keyswitch Position

2

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

3

22-12AWG (0.34-2.5mm

2

) stranded copper wire rated at 75°C or

higher
3/64 inch (1.2mm) insulation maximum
2

Certifications (when
product is marked)

4

UL

UL Listed Industrial Control Equipment (1794-IB10XOB6)

C

UL

US

UL Listed Industrial Control Equipment, certified for US and

Canada (1794-IB16XOB16P)

C

UL

US

UL Listed for Class I, Division 2, Groups A, B, C and D

Hazardous locations certified for US and Canada

(1794-IB16XOB16P)

CSA CSA certified for Class I, Division 2, Groups A, B, C and D

Hazardous locations (1794-IB10XOB6 only)

EEx

4

European Union 94/9/EEC ATEX Directive, compliant with:

EN 50021; Potentially Explosive Atmospheres,

Protection “n” (Zone 2) - (1794-IB10XOB6 only)

CE

5

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity (1794-IB10XOB6,

1794-IB16XOB16P)

C-Tick

4

Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions (1794-IB10XOB6,

1794-IB16XOB16P)

1

Output off-to-on or on-to-off delay is the time from the module issuing an output on or off until the output actually

turns on or off.

2

Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter

time is time from the input signal dropping below the valid level to recognition by the module.

3

You use this category information for planning conductor routing as described in Allen-Bradley

publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

4

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of

Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/.

0

0

10

20

30

40

50

55

60

V

in

O n–state

Voltage

(V dc)

and

Output
Voltage

(V dc)

Ambient Temperature

o

C

The area within the curve represents the safe operating range for the module under
various conditions of user supplied dc supply voltages and ambient temperatures.

= All mounting positions (including normal horizontal, vertical,
inverted horizontal) safe operating range

5

10

15

26.4

30

20

25

31.2