Connecting the Output Wiring
Connect individual output wiring to micro connectors which screw into
mating connectors on the side of the block. Make connections as shown
below.
1
2
3
4
I/O Output Micro Connector
Pin 1 = Not used
Pin 2 = Not used
Pin 3 = Negative
Pin 4 = Output
(View into socket)
Connect the output power wiring to the 3-pin mini connector on the end
of the block.
Important:
The outputs use electronic overcurrent fault protection. Make certain
your output power supply can handle overcurrent events.
1
2
3
Output Power Mini Connector
Pin 1 = Not used
Pin 2 = Positive
Pin 3 = Negative
(View into pins)
Connecting the DeviceNet Wiring
Connect DeviceNet wiring to the 5-pin mini connector on the end of
the block. Connections are shown below.
1
2
3
DeviceNet Mini Connector
Pin 1 = Drain (Bare)
Pin 2 = V+ (Red)
Pin 3 = V– (Black)
(View into pins)
4
5
Pin 4 = CAN–HI (White)
Pin 5 CAN–LO (Blue)