Chapter 2
Wiring and Installation
2–3
The DIO Link must be terminated at each end with an 82 Ohm 1/2 watt
resistor. The resistor is connected across Line 1 and Line 2. In addition,
Chassis Grounding Method One is illustrated below.
Clear
Shield
Blue
82
Ω
Terminating
Resistor
SN
SCANNER
Line 2
Shield
Line 1
Chassis Ground
Clear
Shield
Blue
Terminating
Resistor
82
Ω
Terminating
Resistor
A
2
COM
B
1
SHD
A
2
COM
B
1
SHD
A
2
COM
B
1
SHD
DIO Clear (line 2)
DIO Blue (line 1)
DIO / DH–485 shield
A
2
COM
B
1
SHD
DIO Clear (line 2)
DIO Blue (line 1)
DIO / DH–485 shield
Chassis Grounding
Method 1
1
Because the DIO / DH–485 shields are tied together at each block, you should only connect the shield to chassis
ground in one place. If you choose to ground the shields using Chassis Grounding Method 1 (shown here), do
not use Chassis Grounding Method 2 (shown on page 2–5).