1–2

Configure and Ground I/O Chassis

Publication 1772Ć10.2 - March 1996

Ground I/O Chassis

grounding
electrode
conductor

to grounding
electrode system

equipment grounding
conductor

8 AWG

I/O chassis wall

star washer

ground lug

nut

ground lug

14 AWG

miniĆprocessor with

builtĆin power supply

1771ĆP7

14 AWG

power supply

PLCĆ2/30
processor

ground bus

enclosure wall

power supply

module

ATTENTION: If you use this grounding configuration, do not

make connections to EQUIP GND on the power supply terminal

strips or ground loops could result.