Specifications – Rockwell Automation 1792D-2B2LP INSTL INSTR ARMORBLOCK LP2 User Manual
Page 7

7
2 Sinking Input / 2 Output Module
Publication 1792D-5.25- January 1999
Specifications
Auxiliary Power
Indication
Status
None
No Auxiliary Power
Green
Solid
Auxiliary Power Present
I/O Status Indicators
Function
Module Status Indicator
Point Indicator
Condition
Outputs
Green
Green
None
Yellow
Output not energized
Output energized
Inputs
Green
Green
None
Yellow
No valid input
Valid input
2 Input / 2 Output Module - Cat. No. 1792D-2B2LP
Sinking Input Specifications
Max
Min
Inputs per block
2 - 3 wire or dry contact PNP
Sensor Source Current (per input)
100mA
-
On-state Voltage
25V dc
10V dc
Off-state Voltage
5V dc
On-state Current
10mA
2mA
Off-state Current
1.5mA
Sourcing Output Specifications
Max
Min
Outputs per block
2 labeled O0 and O1
Output Auxiliary Voltage
30V
10V
On-state Voltage Drop
1V
-
On-state Current
0.3A
-
Off-state Leakage
1.5mA
-
Module Current (all outputs)
0.6A
-
Surge Current - for 10ms,
repeatable every 2s
0.6A
-
No Load Sense Current (On-state)
0.18A
-
General Specifications
Indicators
Network Status - red/green
Module Status - red/green
Auxiliary Power - green
Point LED - yellow