Worst case accuracy for the thermocouple/mv module, Type l thermocouple – Rockwell Automation 1794-IT8,D17946.5.7 Thermocouple/Millivolt Input Module User Manual
Page 62

Specifications
A–8
Publication 1794-6.5.7 – March 1997
Type L Thermocouple
10–100Hz
250Hz
500Hz
1000Hz
Resolution
C
F
0.13
32.2
1.06
33.9
8.51
47.3
68.09
154.5
0.08
32.1
0.66
33.1
5.31
41.5
42.49
108.4
0
0.03
32.0
0.26
32.4
2.13
35.8
17.04
62.6
0.18
32.3
1.46
34.6
11.71
53.0
93.69
200.6
–200
–328
–150
–238
0
32
50
122
100
212
200
392
400
752
500
932
600
1112
700
1292
Temperature
C
F
300
572
800
1472
–100
–148
Worst Case Accuracy for the Thermocouple/mV Module
Input Type
Accuracy
@ 25
o
C
Accuracy
@ 77
o
F
Temperature Drift
(0–60
o
C) (32–
o
F)
B
+3.70
o
C
+6.66
o
F
+0.710
o
C/
o
C
+0.710
o
F/
o
F
E
+0.51
o
C
+0.92
o
F
+0.104
o
C/
o
C
+0.104
o
F/
o
F
J
+0.68
o
C
+1.22
o
F
+0.130
o
C/
o
C
+0.130
o
F/
o
F
K
+1.00
o
C
+1.80
o
F
+0.186
o
C/
o
C
+0.186
o
F/
o
F
R
+3.16
o
C
+5.69
o
F
+0.601
o
C/
o
C
+0.601
o
F/
o
F
S
+3.70
o
C
+6.67
o
F
+0.651
o
C/
o
C
+0.651
o
F/
o
F
T
+0.67
o
C
+1.21
o
F
+0.174
o
C/
o
C
+0.174
o
F/
o
F
N
+1.07
o
C
+1.93
o
F
+0.223
o
C/
o
C
+0.223
o
F/
o
F
C
+3.40
o
C
+6.12
o
F
+0.434
o
C/
o
C
+0.434
o
F/
o
F
L
+0.58
o
C
+1.35
o
F
+0.119
o
C/
o
C
+0.119
o
F/
o
F
mV
+39
µ
V
+39
µ
V
+7.812
µ
V/
o
C
+14.06
µ
V/
o
F