Interpret Status Indicators
Refer to the following diagram and table for information on how to interpret the
status indicators.
Indicator Status for Modules
Status
Description
Recommended Action
Module status
Off
No power applied to device.
Apply power to device.
Green
Device operating normally.
None.
Flashing green
Device needs commissioning
due to missing, incomplete, or
incorrect configuration.
Configure device properly.
Flashing red
Recoverable fault.
Cycle power to device. If
condition persists, replace
device.
Red
Unrecoverable fault – may
require device replacement.
Replace device.
Flashing red/green Device is in self-test mode.
None.