Universal Serial Bus (USB) to DH-485 Interface Converter 13

Publication 1747-IN063C-EN-P - January 2006

8. The 1747-UIC interface converter operates at 19.2 Kbps only, so set the Baud

Rate to 19200.

Do not click AutoConfigure.

9. Assign the 1747-UIC interface converter an unused station number on the

DH-485 network to which you are connecting.

The interface converter cannot go online to a DH-485 network if it’s
assigned station number is already being used. Station number 0 is typically
reserved for use by RSLinx, but any station number from 0 to 31 is valid.

10. Click OK.

The 1747-UIC interface converter appears on the network at node 0, as

shown in the example below.

Uninstall the Drivers

To uninstall the 1747-UIC drivers from a computer:

1. Choose Add/Remove Programs from the Windows Control Panel.

2. Select FTDI USB Serial Converter Drivers.

IMPORTANT

Always stop the RSLinx RS-232 DF1 driver or shut down
RSLinx prior to unplugging the interface converter from the
computer’s USB port.