Specifications, Specifications 21 – Rockwell Automation 1734-IM2_IM4 POINT I/O 220V AC Input Module User Manual
Page 21

POINT I/O 220V ac Input Module 21
Publication
1734-IN008C-EN-E - January 2007
Specifications
220V ac Input Modules - 1734-IM2 and 1734-IM4
Attribute
Value
Number of Inputs
1734-IM2: 2 (1 group of 2) nonisolated, sink
1734-IM4: 2 (1 group of 4) nonisolated, sink
On-state Voltage Range,
Min
159V ac
On-state Voltage Range,
Nom
220V ac
On-state Voltage Range,
Max
264V ac
On-state Current, Min
6.2 mA @ 159V ac, 60 Hz
On-state Current, Nom
8.5 mA @ 220V ac, 60 Hz
On-state Current, Max
10.2 mA @ 264V ac, 60 Hz
Off-state Voltage, Max
43V ac
Off-state Current, Max
2.9 mA
Input Impedance, Nom
22.3 k
Ω
Delay Time
(1)
Off to On and On to Off
(1)
Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input
on-to-off filter time is the time from the input signal dropping below the valid level to recognition by
the module. Due to the randomness of the ac line cycle measurement capture point and response time
of the hardware filter, the maximum hardware delay is 20 ms plus the filter time.
20 ms hardware filter plus 1…64 ms digital filter
programmable in increments of 1 ms
Keyswitch Position
8