Before installing the power supply, you should:
•
mount the I/O chassis that the power supply will be connected to.
See the Universal I/O Chassis Installation Data (1771-2.210) for
information on mounting the I/O chassis.
•
set the power supply configuration jumper on the I/O chassis.
The 1771-P7 is an external power supply. Set the configuration
jumper to the N position.
N
Y
Using
Power Supply
Module in
the Chassis?
12620ĆI
The power supply has a D-shell power connector that provides
power to the I/O chassis backplane.
A1
3
4
5
A2
1
2
A1 backplane common
A2 backplane +5V dc
1
no connection
2
backplane processor enable
3
backplane +5V dc sense
4
backplane signal ground sense
5
no connection
bottom view of power supply
13445
If you have this I/O chassis
Use this power cable
To connect a 1771ĆP7 mounted
1771ĆA3B
1771ĆCP2
within 1.52m (5ft) of the I/O chassis
1771 A1B A2B A3B1
A4B
1771ĆCP1
within 0.32m (1.04ft) on the leftĆside of the I/O chassis
1771ĆA1B, ĆA2B, ĆA3B1, or ĆA4B
1771ĆCP3
(right angle connector)
within 1.68m (5.5ft) of the I/O chassis
Install the 1771ĆP7 and
Connect Backplane Power