Devicenet connector wiring, Communicating with your module, Default data for the 1734d-ia16 – Rockwell Automation 1734D-IA16S PointBlock ac 16-Input Module Installation Notes User Manual
Page 7
Advertising

POINTBlock ac 16 Input Module 7
Publication 1734D-IN001A-EN-P - May 2001
DeviceNet Connector Wiring
Communicating with Your Module
I/O messages are sent to (consumed) and received from (produced)
the POINTBlock I/O modules. These messages are mapped into the
processor’s memory. This POINTBlock I/O input module produces 2
bytes of input data (scanner Rx). It does not consume I/O data
(scanner Tx).
Default Data for the 1734D-IA16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Produces
(Rx)
I15
I14
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
I0
Consumes
(Tx)
No consumed data
Where:
I0 = channel 0, I1 = channel 1; 0 = off, 1 = on
DeviceNet
connection
Red
White
Bare
Blue
Black
-V
42132
+V
CAN - High
Shield
CAN - Low