AC (220V) Output Module Cat. No. 1771-OMD Series B

Publication 1771Ć5.26 - February 2000

Driving an Input with an Output

(Cat. No. 1771ĆIM)

Note: 1771ĆOMD output voltĆ

age range is 184Ć250V ac.

However, the onĆstate voltage

range of the 1771ĆIM is

184Ć276V ac.

L2

ac Low

10Kohm 10W reĆ

sistor

L1

220V ac High

AC/DC (220V)

Input Module

AC (220V)

Output Module

(Cat. No. 1771ĆOMD)

11926ĆI

The front panel of your module contains one green, module active
indicator, 16 red status indicators and one red fuse-blown indicator.
The 1771-OMD/B performs diagnostics in a handshaking mode
when first powered up. Upon successful completion of the
diagnostics, the green module active indicator lights. It turns off if a
fault occurs in the data paths or the opto-isolators.

The red status indicators are provided for system logic side
indication of individual outputs. When a red status indicator lights,
voltage is present on the terminal.

The red fuse-blown indicator is lit when the fuse in the module has
cleared or been removed.

Interpreting the Status

Indicators

ACTIVE

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Module Active

Indicator

(green)

00 to 17 Status

Indicators (red)

11927ĆI

FUSE

Fuse Blown

Indicator

(red)