Wiring Input Devices to the NR8 Module
To wire your NR8 module, follow these steps.
1. At each end of the cable, strip some casing to expose the individual wires.
2. Trim the signal wires to 5.08-cm (2-in.) lengths. Strip about 4.76 mm (3/16
in.) of insulation away to expose the end of the wire.
3. At one end of the cable twist the drain wire and foil shield together, bend
them away from the cable, and apply shrink wrap. Then earth ground at the
frame ground of the chassis.
4. At the other end of the cable, cut the drain wire and foil shield back to the
cable and apply shrink wrap.
5. Connect the signal wires to the 1746-NR8 terminal block and the input.
6. Repeat steps 1 through 5 for each channel on the 1746-NR8 module.
2-Conductor Shielded Cable
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Drain Wire
Drain Wire
Foil Shield
Foil Shield
3-Conductor Shielded Cable
(See Step 4.)
(See Step 4.)
(See step 3.)