5. If necessary, push the bus lever back slightly to clear the bus locking tab (3).

Use your fingers or a small screwdriver.

6. To allow communication between the module and the cable connector,

move the bus lever firmly to the left (4) until it clicks. Ensure that it is locked
firmly in place.

ATTENTION

!

When attaching cables, it is very important that the bus
connectors are securely locked together to ensure proper
electrical connection.

Specifications

Approximate Shipping
Weight (with carton)

3-foot cables: 350 g (0.77lbs.)
1-foot cables: 300 g (0.66 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (32°F to +140°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 inches maximum peak-to-peak
Relay Operation: 2G

Shock

Operating: 30G panel mounted (20G DIN rail mounted)
Relay Operation: 7.5G panel mounted (5G DIN rail mounted)
Non-Operating: 40G panel mounted (30G DIN rail mounted)

Agency Certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous Environment
Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)