ATTENTION

Do not attempt to increase load current or wattage
capability beyond the rating by connecting two or
more outputs in parallel. The slightest variation in
output relay switching time may cause one set of
contacts to switch the total load current.

You can use the 1771-OWN output module to drive an input of a
120V ac input module (1771-IA, -IA2, -IAD) to indicate status of
turning on a motor starter as shown below, for example, but you
must connect a 15K, 2W resistor between the output and L2
(common). Inputs configured with the output module are not isolated
from each other.

Driving an Input Module with a 1771-OWN Output Module

120V AC Input Module

(Cat. No. 1771ĆIAD)

Selectable Contact Output Module

(Cat. No. 1771ĆOWN)

ac High

ac Low

L1

L2

Input 00

Input 01

Input 02

Input 03

Input 04

Input 05

Input 06

Input 07

Input 10

Input 11
Input 12

Input 13

Input 14

Input 15

Input 16

Input 17

1
2
3
4
5
6
7
8
9
10
11
12
13
14

15
16
17
18
19
20

21

Output 0

Output 2
Output 4

Output 6

Not used
Output 10

Output 12

Output 14

Output 16

Not used

Output 0

Output 2

Output 4

Output 6

Not used

Output 10

Output 12
Output 14

Output 16
Not used

Common 0

Output 1

Output 3

Output 5

Output 7

Common 1

Output 11

Output 13
Output 15

Output 17
Common 2

Output 1
Output 3
Output 5

Output 7

Common 3

Output 11
Output 13

Output 15

Output 17

10540ĆI

15K ohm, 2W

resistor

If multiple power supplies are used, do not exceed the specified isolation voltage.