General Specifications - 1794-IG16, 1794-OG16

Specification

Description

Terminal base screw torque

Determined by installed terminal base

Dimensions (with module installed)

H x W x D

94 x 94 x 69 mm

3.7 x 3.7 x 2.7 inches

External dc power supply voltage

5V dc nominal

External dc power voltage range

4.5...5.5V dc

(includes 50mV p-p ripple)

External dc power supply current

1794-IG16 - 210mA max @ 5V dc

1794-OG16 - 100mA @ 5V dc

North American temp code

T4A

Keyswitch position

1

Enclosure type rating

None (open-style)

Wire type

Shielded (Power and I/O)

Wire size

Determined by installed terminal base

Wiring category

(1)

3- on signal ports

2- on power ports

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications

Specification

Description

Operating temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0...55 °C (32…131 °F)

Storage temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10...500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):

Operating 30g

Non-operating 50g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2k V at 5kHz on power ports

±2k V at 5kHz on signal ports

Surge transient immunity

IEC 61000-4-5:

±2 kV line-earth(CM) on power ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certifications

(when product is marked)

(1)

(1)

See the Product Certification link at

www.ab.com

for Declarations of Conformity, Certificates, and other certification

details.

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada.

See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,

certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Advertising