3

Publication 1794-IN102B-EN-P - June 2004

1794-TB2, -TB3 and -TB3S Terminal Base Wiring for 1794-IA8,
IA8K and -IA16

1794-TBN Terminal Base Wiring for 1794-IA8, IA8K

and -IA16

Connecting Wiring for the 1794-IA16

1. For 1794-TB3, or -TB3S - Connect individual input wiring to

numbered terminals on the 0-15 row (A) as indicated in the table
below .

For 1794-TBN - Connect individual input wiring to even numbered
terminals on the 16-33 row (B), and to the odd numbered terminals
on the 34-51 row (C) as indicated in the table below.

2. For 1794-TB3, or -TB3S - Connect the associated 120V ac power

lead (L1) of the input device to the corresponding terminals on the
34-51 row (C) for each input as indicated in the table below. (The
120V power terminals of row (C) are internally connected together.)


For 1794-TBN - An external terminal strip is needed to distribute
120V ac power (L1) to each device.

3. Connect 120V ac power (L1)to terminal 34 on the 34-51 row (C).

4. Connect 120V ac common (L2) to terminal 16 on the 16-33 row (B).

5. If daisychaining power to the next terminal base, connect a jumper

from terminal 51 (+120V ac L1) on this base unit to terminal 34 on
the next base unit.

6. If continuing ac common to the next base unit, connect a jumper

from terminal 33 (120V common L2) on this base unit to terminal 16
on the next base unit.

Terminal Base Wiring for 1794-IA16

Connecting Wiring for the 1794-IA8I

1. For 1794-TB2, -TB3, or -TB3S - Connect individual input wiring to

even numbered terminals on the 0-15 row (A) as indicated in the table
below .

For 1794-TBN - Connect individual input wiring to even numbered
terminals 0-14 on the 16-33 row (B) as indicated in the table below.

2. For 1794-TB2, -TB3, or -TB3S - Connect the associated 120V ac

common (L2) of the isolated supply to the corresponding odd
numbered terminals on the 0-15 row A for each input as indicated in
the table below.

For 1794-TBN - Connect the associated 120V ac common lead (L2)
of the isolated supply to the corresponding odd numbered terminal
1-15 on the 34-51 row (C) as indicated in the table below.

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Inputs

Commons

(1794-TB3 shown)

L2

L1

Voltage

A

B

C

L2

Connect 120V ac L1 power to terminal C-34
Connect 120V ac common L2 to terminal B-16

Use B-33 and C-51 for daisychaining to the next terminal base unit

L1

(Terminals C-35 thru C-50 not available on the 1794-TB2.)

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

51

33

34

L1

L2

L1

L2

B

C

Even Numbered I/O Terminals 0 thru 14

Odd Numbered I/O Terminals 1 thru 15

(1794-TBN shown)

L1 = 120V ac - Connect to terminal C-34
L2 = 120V ac common - Connect to terminal B-16

Use B-33 and C-51 for daisychaining to the next terminal base unit

Input
Channel

Input Terminal

1794-TB3, -TB3S

Input Terminal

1794-TBN

120V ac
Supply (L1)

1

Input 0

A-0

B-0

C-35

Input 1

A-1

C-1

C-36

Input 2

A-2

B-2

C-37

Input 3

A-3

C-3

C-38

Input 4

A-4

B-4

C-39

Input 5

A-5

C-5

C-40

Input 6

A-6

B-6

C-41

Input 7

A-7

C-7

C-42

Input 8

A-8

B-8

C-43

Input 9

A-9

C-9

C-44

Input 10

A-10

B-10

C-45

Input 11

A-11

C-11

C-46

Input 12

A-12

B-12

C-47

Input 13

A-13

C-13

C-48

Input 14

A-14

B-14

C-49

Input 15

A-15

C-15

C-50

120V ac L1

Power terminals C-34 thru C-51 (C-34 and C-51 on -TBN) are
internally connected together. Connect 120V ac L1 to C-34

120V ac L2

Common terminals B-16 thru B-33 (B-16 and B-33 for -TBN) are
internally connected together. Connect 120V ac common L2 to
terminal B-16

1

When using the 1794-TBN, an external terminal strip is needed to connect the 120V ac power

connections.

IMPORTANT

Individual isolated 120V ac L1 power leads must
be run externally to each of the input devices.