FLEX Integra 16 Source Input Module

Publication 1793-5.10 - December 1999

Setting the Input Delay Time

You can select the input delay time (DT) for channels 00 thru 11 and
channels 12 thru 15. Select the input delay time by setting the
corresponding bits in the output image table (complementary word) for the
module.

For example, to set a delay time of 4ms for an input module at address rack
1, module group 0, set bits 05, 04, 03, 02, 01 and 00 as shown below.

Input Delay Times

Important: Input and output wiring must be in accordance with Class I,

Division 2 wiring methods and in accordance with the
authority having jurisdiction

02

01

00

Filter Time for Inputs 00-11

Selected
Filter Time

05

04

03

Filter Time for Inputs 12-15

0

0

0

Filter Time 0 (default)

250

μs

0

0

1

Filter Time 1

500

μs

0

1

0

Filter Time 2

1ms

0

1

1

Filter Time 3

2ms

1

0

0

Filter Time 4

4ms

1

0

1

Filter Time 5

8ms

1

1

0

Filter Time 6

16ms

1

1

1

Filter Time 7

32ms

15 14 13 12

11 10 09 08 07 06 05 04 03 02 01 00

1

0

0

= 44 Octal or 36 decimal

Write delay time on system startup.

Write DT to complement

of input module.

Fill File
Source

Destination
Length

3

#O:010

1

I:000

00

FLL

O:010

Dec.

41335B

1

0

0

DT 00-11