Rockwell Automation 1734-OV2E_4E_8E POINT I/O Protected Sink Output Module Installation Instructions User Manual
Page 22
 
22 POINT I/O Protected Sink Output Module
Publication
1734-IN585C-EN-E - December 2005
Indication
Probable Cause
Recommended Action
Network Status
Off
Device is not online.
- Device has not completed 
dup_MAC_id test.
- Device not powered - check module 
status indicator.
Apply power to the device, 
wait for MAC-id to 
complete, and correct, if 
needed. 
Flashing Green
Device is online but has no 
connections in the established state.
None - device is in Idle or 
Program mode.
Solid Green
Device is online and has connections 
in the established state.
None
Flashing Red
One or more I/O connections are in 
timed-out state.
Check for I/O module 
failure, and correct, as 
needed.
Solid Red
Critical link failure - failed 
communication device is present. 
Device detected error that prevents it 
communicating on the network.
1. Reinstall adapter and 
terminal base, if 
improperly installed.
2. Correct duplicate 
MAC_id, if needed. 
Flashing Red/Green
Communication faulted device - the 
device has detected a network access 
error and is in communication faulted 
state. Device has received and 
accepted an Identify Communication 
Faulted Request - long protocol 
message.
Verify that adapter is 
properly installed, and 
reinstall, as needed.
I/O Status
Off
All outputs are inactive.
None
Solid Yellow
One or more outputs are active and 
under control.
None
Solid Red
Overload, short circuit, or 
overtemperature detected (On-State 
only).
Remove overload, short 
circuit, or overtemperature 
condition.