14 DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A
Publication
1732D-IN011A-EN-E - April 2009
Module Status
Status
Description
Recommended action
Off
There is no power applied to the 
device.
Apply power to the device.
Green
Device is operating normally.
None.
Flashing 
Green
Device needs commissioning due to 
missing, incomplete, or incorrect 
configuration.
Check your configuration and cycle 
power.
Flashing Red
Recoverable fault – input or output 
short circuit.
Check your input devices and 
check your output devices and 
cycle power.
Red
Critical fault – device timed out or 
has an unrecoverable fault.
Cycle power to the device. If that 
does not fix the fault, contact your 
Rockwell Automation 
representative. The device may 
need to be replaced.
Auxiliary Status
Status
Description
Recommended action
Off
There is no auxiliary power applied 
to the device.
Apply auxiliary power to the 
device.
Green
There is auxiliary power applied to 
the device.
None.
I/O Status
Status
Description
Recommended action
Off
Output is not energized or input is 
not valid.
None.
Yellow
Output is energized or input is valid.
None.