AC/DC (120V) Input Module

7

Publication 1771ĆIN023B-EN-P - August 2002

Connect your I/O devices to the field wiring arm (cat. no. 1771-WH)
shipped with the module.

1. Connect one terminal of your 2-wire input device to terminals 00

thru 17. Connect L1 (high) ac/dc line to the other terminal of your
input devices.

2. Connect terminal E to the L2 (low) ac/dc return. Terminals A thru

D are not used. Use stranded 14 gauge wire to minimize the
voltage drop over long cable distances.

Terminal A

Terminal B

Terminal C

Terminal D

(Actual wiring runs in this direction.)

Input 00

Input 01

Input 02

Input 03

Input 04

Input 05

Input 06

Input 07

Input 10

Input 11

Input 12

Input 13

Input 14
Input 15

Input 16

Terminal E

Input 17

L1

ac/dc High

ac/dc Low

A

B

C
D

00

01

02
03

04
05

06

07

10

11

12
13

14

15
16

E

17

10589ĆI

L2

Field Wiring Arm

Cat. No. 1771ĆWH

IMPORTANT

You can use an AC (120V) Output Module (cat.
no. 1771-OAD) to directly drive terminals on an
AC/DC (120V) Input Module (cat. no.
1771-IAD) as shown below.

Connect Wiring to the

FieldWiring Arm