Rockwell Automation 1769-OB32 Installation Instructions User Manual

Page 20

Advertising
background image

20 Compact 32-point Solid-state 24V dc Source Output Module

Publication 1769-IN031A-EN-P - April 2003

The graph below illustrates that the duration of the transient is proportional to the
load current. Therefore, as the on-state load current increases, the transient pulse
decreases. Power-up transients do not exceed the time duration shown below, for
the amount of loading indicated, at 60°C (140°F).

0.4

1.0

0.9

0.8

0.7

0.6

0.5

0.3

0.2

0.1

0.0

1000

900

800

700

600

500

400

300

200

100

1

30519-M

On-State Load Current (mA)

Transient Pluse Duration as a Function of Load Current

Time-Duration of transient (mS)