Rockwell Automation 1794-IC16_OC16 FLEX I/O 48V dc Input and Output Modules Inst. Inst. User Manual

Page 4

Advertising
background image

4

Publication 1794-IN105A-EN-P - April 2004

Derating Curve for the 1794-IC16

Nominal Input Current

5.0mA @ 48V dc

Isolation Voltage

Tested at 1900V dc for 1s between user and system
No isolation between individual channels

Flexbus Current

25mA

Power Dissipation

6.4W maximum @ 60V dc

Thermal Dissipation

Maximum 21.9 BTU/hr @ 60V dc

Input Filter Time

1

Off to On

On to Off

Minimum filter time of 1ms plus selected filter time of:
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms default - Selectable using configuration word 3

Specifications - 48V dc 16 Output Module, Cat. No. 1794-OC16

Number of Outputs

16, nonisolated, sourcing

Module Location

Cat. No. 1794-TB2, -TB3, or -TB3S Terminal Base Unit

On-state Voltage
Range

30V dc minimum

48V dc nominal

60V dc maximum @ 45

o

C

55V dc maximum @ 55

o

C

Output Current Rating

8.0A (16 outputs @ 0.5A)

Off-state Voltage

60V dc maximum

On-state Current

2.0mA minimum per channel
500mA maximum per channel

Surge Current

4A for 10ms, repeatable every 2s

Off-state Leakage

1.0mA maximum

On-state Voltage Drop

1.0V dc maximum @ 0.5A

Isolation Voltage

Tested at 1900V dc for 1s between user and system
No isolation between individual channels

Output Signal Delay

2

Off to On

On to Off

0.5ms maximum
1.0ms maximum @ 25

o

C

2.0ms maximum @ 55

o

C

Flexbus Current

80mA

Power Dissipation

3.7W maximum @ 60V dc

Thermal Dissipation

12.6 BTU/hr @ 60V dc

Fusing

3

SANO MQ2 - 2A, 150V ac normal blow

General Specifications

1794-IC16

1794-OC16

Terminal Base Screw
Torque

7 pound-inches (0.8Nm)

Dimensions (with module
installed)

3.7H x 3.7W x 2.7D inches
94H x 94W x 69D mm

Indicators (field side
indication)

16 yellow status indicators

(customer device driven)

16 yellow status indicators

(logic driven)

External dc power

Supply voltage

Voltage range

Input Supply Current

48V dc nominal
30 to 60V dc (includes 5% ac
ripple)
51mA @ 30V dc

82mA @ 48V dc

107mA @ 60V dc

48V dc nominal
30 to 60V dc (includes 5% ac
ripple)
13mA @ 30V dc

21mA @ 48V dc

27mA @ 60V dc

Keyswitch Position

2

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
8kV air discharges

4kV contact discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

±2kV at 5kHz on power ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

±1kV line-line(DM) and ±2kV line-earth(CM) on power ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

4

12 to 22AWG (4 to 0.25mm

2

) stranded copper wire rated at 75°C or

higher
3/64 inch (1.2mm) insulation maximum
2

Certifications (when
product is marked)

5

UL

UL Listed Industrial Control Equipment

CSA CSA certified for Class I, Division 2, Groups A, B, C and D

Hazardous locations

EEx

5

European Union 94/9/EEC ATEX Directive, compliant with:

EN 50021; Potentially Explosive Atmospheres,

Protection “n” (Zone 2)

CE

5

European Union 89/336/EEC EMC Directive,
compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

5

- Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

1

Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter

time is time from the input signal dropping below the valid level to recognition by the module.

2

Delay time is the time from receipt of an output on or off command to t he output actually turning on or off.

3

Module outputs are not fused. Fusing is recommended. If fusing is desired, you must supply external fusing.

4

You use this category information for planning conductor routing as described in Allen-Bradley

publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

5

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/.

0

35

30

45

40

10

20

30

40

50

55

60

V

in

On-state

Voltage

(V dc)

Ambient Temperature

o

C

The area within the curve represents the safe operating range for the module under
various conditions of user supplied 48V dc supply voltages and ambient temperatures.

= Normal mounting safe operating range, (includes ).

= Other mounting positions (including inverted horizontal) safe operating range

41

29

50

55

60

Normal Mounting - Horizontal

Other Mounting (including Vertical, and Inverted Horizontal Mounting)

Voltage (max.)

Temperature (max.)

Normal Other

60

55

50

41

55

55

29

42

55