background image

Publication 1771-IN072B-EN-P - December 2004

4

PN 957944-28

Supersedes Publication 1771-2.116 - April 1992 and 1771-IN072A - January 2001

© 2004 Rockwell International Corporation. Printed in the U.S.A.

4. Replace the fuse holder in the field wiring arm as shown above.

5. Reapply power to the wiring arm.

Specifications

WARNING

The 1771-WHF and 1771-WHFB are not suitable for use
in Class I Division 2 Groups A, B, C, D Environments.

Catalog Number

1771-WHF (3 A) and 1771-WHFB (1.5 A)

Dimensions

8.265H x 1.224W x 2.0D (inches)

209H x 31W x 51D (millimeters)

Conductors

Wire Size - 14…20 AWG (2.5mm

2

…0.5mm

2

), copper only

stranded or solid, rated at 75

o

C or higher,

3/64 inch (1.22mm) insulation

Category - Refer to specific module installation instructions

Fuses

1771-WHF - Littelfuse 2AG 3 A Part No. 225003

1771-WHFB - Littelfuse 2AG 1.5 A Part No. 22501.5

Optional Fuse Pak

1771-WHF - Cat. No. 1771-FD: contains 2 fuse holders and 8 2AG 3 A
fuses
1771-WHFB - Cat. No. 1771-FD2: contains 2 fuse holders and 8 2AG
1.5 A fuses

Wiring Arm Screw Torque

9 pound-inches

Terminal Rating

Terminals A-D rated for 8 A @ 250V

1771-WHF - Terminal 00…17 - 3.0 A, 250V per terminal with a
maximum of 12 A combined for terminals 00…17 derated linearly
from 10 °C to 2 A per terminal at 60 °C.

1771-WHFB - Terminal 00…17 - 1.5 A, 250V per terminal with a
maximum of 12 A combined for terminals 00…17.