Input specifications – Rockwell Automation 1769-IQ32 Install Instr User Manual

Page 14

Advertising
background image

14 Compact 32-point 24V dc Sink/Source Input Module

Publication 1769-IN032A-EN-P - April 2003

Input Specifications

Specification

1769-IQ32

Voltage Category

24V dc (sink/source

(1)

)

(1)

Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field
devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and
sourcing output module circuits are the commonly used options.

Operating Voltage Range

10 to 30V dc at 30°C (86°F)

10 to 26.4V dc at 60°C (140°F)

Number of Inputs

32

Bus Current Draw (max.)

170 mA at 5V dc (0.85W)

Heat Dissipation

4.6 Total Watts (The Watts per point, plus the minimum Watts, with all
points energized.)

Signal Delay (max.)

On Delay: 8.0 ms

Off Delay: 8.0 ms

Off-State Voltage (max.)

5V dc

Off-State Current (max.)

1.5 mA

On-State Voltage (min.)

10V dc

On-State Current (min.)

2.0 mA

Inrush Current (max.)

250 mA

Nominal Impedance

5.2kohm at 24V dc, 6.1kohm at 30V dc

IEC Input Compatibility

Type 1+

Power Supply Distance Rating

8 (The module may not be more than 8 modules away from the power
supply or controller.)

Input Point to Bus (Compact Bus)
Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.

75V dc working voltage (IEC Class 2 reinforced insulation)

Isolated Groups

Group 1: inputs 0 to 7

Group 2: inputs 8 to 15

Group 3: inputs 16 to 23

Group 4: inputs 24 to 31

Isolated groups operate in either sink or source configurations.

Input Group to Input Group Isolation

Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.

75V dc working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

68

Advertising