11

Publication 1769-IN007B-EN-P

Specifications

General Specifications

Specification

Value

Dimensions

118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm

4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.

Approximate Shipping Weight
(with carton)

270g (0.6 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (32°F to +140°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 inches maximum
peak-to-peak

Relay Operation: 2G

Shock

Operating: 30G panel mounted (20G DIN rail mounted)

Relay Operation: 7.5G panel mounted (5G DIN rail
mounted)

Non-Operating: 40G panel mounted (30G DIN rail
mounted)

Agency Certification

• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C,
D (UL 1604, C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

• ESD Immunity (IEC1000-4-2)

• 4kV contact, 8 kV air, 4 kV indirect

• Radiated Immunity (IEC1000-4-3)

• 10 V/m, 80 to 1000 MHz, 80% amplitude modulation,

+900 MHz keyed carrier

• Fast Transient Burst (IEC1000-4-4)

• 2 kV, 5 kHz

• Surge Immunity (IEC1000-4-5)

• 2 kV common mode, 1 kV differential mode

• Conducted Immunity (IEC1000-4-6)

• 10V, 0.15 to 80 MHz

1

1. Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range

is 30 MHz to 1000 MHz.