Step 2

Set the 1769-SM2 module Configuration Mode switch and Operating
Mode (Single/Multi-Drive) switch to appropriate positions. For complete
switch setting details, see the 1769-SM2 module User Manual.

Step 3

Assemble the 1769-SM2 module to the controller. It can be attached to
adjacent controller modules before or after mounting. For mounting
instructions, see Step 4A (Panel Mounting) or Step 4B (DIN Rail
Mounting). To work with a system that is already mounted, see Step 5.

A. Disconnect power.

B. Install the 1769-SM2 module within 4 slots of the power supply.

C. Check that the bus lever (item 1) of the 1769-SM2 module is in the

unlocked (fully right) position.

D. Use the upper and lower tongue-and-groove slots (item 2) to secure the

modules together.

E. Move the 1769-SM2 module back along the tongue-and-groove slots

until the bus connectors (item 3) line up with each other.

F. Use your fingers or a small screwdriver to push the bus lever back

slightly to clear the positioning tab (item 4).

G. Move the 1769-SM2 module’s bus lever fully to the left (item 5) until it

clicks. Ensure it is locked firmly in place.

H. Attach an end cap terminator (item 6) to the last module in the system

by using the tongue-and-groove slots as before.

I. Lock the end cap bus terminator (item 7).

Important: A 1769-ECR or 1769-ECL right or left end cap must be used

to terminate the end cap of the serial communication bus.

7

6

5

4

2

1

2

3

!

ATTENTION: Risk of equipment damage exists. When
attaching the 1769-SM2 module to a Compact I/O system, it is
very important that the bus connectors are securely locked
together to ensure proper electrical connection. Failure to do
this may cause an electrical arc, which can cause personal
injury or equipment damage.