Default configuration – Rockwell Automation 1771-IL/B , D17716.5.91 ISOLATED ANALOG INPUT Module User Manual
Page 34

Module Configuration
Chapter 4
4-10
If a write block with all zeroes is written to the module, the default
selections will be:
1 to 5V dc or 4 to 20mA (depends on voltage/current selection jumper)
BCD data format
no real time sampling (RTS)
no digital filter
no
scaling
no
alarms
Note: Input data is set to 0 until an initial block transfer write is received
by the module.
Figure 4.4
Word Assignments for the Isolated Analog Input Module
(1771-IL series B)Block Transfer Write
Decimal Bits
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal Bits
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
1
Range Selection Bits for Channels 1 through 8
Word 1
8
7
6
5
4
3
2
1
2
Real Time Sampling
Data
Format
BTW
Format
Digital Filter
3
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
3
Sign bits, maximum scaling values
Sign bits, minimum scaling values
4
Channel 1 - minimum scaling
5
Channel 1 - maximum scaling
6
Channel 2 - minimum scaling
7
Channel 2 - maximum scaling
8
Channel 3 - minimum scaling
9
Channel 3 - maximum scaling
10
Channel 4 - minimum scaling
11
Channel 4 - maximum scaling
12
Channel 5 - minimum scaling
13
Channel 5 - maximum scaling
14
Channel 6 - minimum scaling
15
Channel 6 - maximum scaling
16
Channel 7 - minimum scaling
Default Configuration