Specifications

Mounting Dimensions

Status Indicator

Off

No power

Flashing Green

On-line but not connected

Green

On-line, link okay, connected

Flashing Red

I/O module removed, wrong I/O module
inserted, FLASH program update in progress

Red

Critical - adapter failure

Specifications - Cat. No. 1794-ACN15 and -ACNR15

I/O Capacity

8 modules

Input Voltage Rating

24V dc nominal
19.2V to 31.2 V dc (includes 5% ac ripple)

Current Draw

450mA maximum; 330mA @ 24V dc

Inrush Current

23A for 2ms

Communication Rate

5M bps

Indicators

I/O Status - red/green
Comm A - red/green
Comm B - red/green

Flexbus Output Current

640mA maximum

Isolation Voltage

Tested at 850V dc for 1s between user power and flexbus

Power Dissipation

4.6W maximum @ 19.2V dc

Terminal Screw Torque

7 pound-inches (0.8Nm)

Dimensions

3.4H x 3.7W x 2.7D inches
87H x 94W x 69D mm

General Specifications

Environmental Conditions

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
10V/m with 200 50% Pulse 100% AM at 900MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on communication ports

Surge Transient Immunity

IEC 61000-4-5:
±2kV line-earth(CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

Category

1

22-12AWG (0.34mm

2

-2.5mm

2

) stranded copper wire rated at 75°C or

higher
3/64 inch (1.2mm) insulation maximum
2

LED Indications

Probable Cause

ControlNet Cable

Belden RG-6/U

Certifications (when product is
marked)

2

C

UL

US

UL Listed Industrial Control Equipment, certified for US

and Canada

UL

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous

Locations

C

UL

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous

Locations, certified for Canada

CSA CSA certified Process Control Equipment

CSA CSA certified for Class I, Division 2, Groups A, B, C and D

Hazardous locations

EEx

2

European Union 94/9/EEC ATEX Directive, compliant with:

EN 50021; Potentially Explosive Atmospheres,

Protection “n” ( Zone 2)

CE

2

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

2

Australian Radiocommunications Act compliant with

AS/NZS CISPR 11, Industrial Emissions

1

You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

2

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/.

3.4

(87)

3.2

(80)

3.7

(94)

2.0

(50)

1.2

(30)

A

B

1794-ACN15, -ACNR15

3.4H x 3.7W x 2.7D
(87H x 94W x 69D)

(1794-ACNR15

A = DIN rail

B = Secure DIN rail about every 200mm

shown)